Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 1. sayfa 1 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 2. sayfa 2 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 3. sayfa 3 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 4. sayfa 4 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 5. sayfa 5 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 6. sayfa 6 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 7. sayfa 7 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 8. sayfa 8 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 9. sayfa 9 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 10. sayfa 10 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 11. sayfa 11 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 12. sayfa 12 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 13. sayfa 13 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 14. sayfa 14 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 15. sayfa 15 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 16. sayfa 16 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 17. sayfa 17 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 18. sayfa 18 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 19. sayfa 19 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 20. sayfa 20 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 21. sayfa 21 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 22. sayfa 22 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 23. sayfa 23 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 24. sayfa 24 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 25. sayfa 25 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 26. sayfa 26 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 27. sayfa 27 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 28. sayfa 28 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 29. sayfa 29 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 30. sayfa 30 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 31. sayfa 31 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 32. sayfa 32 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 33. sayfa 33 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 34. sayfa 34 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 35. sayfa 35 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 36. sayfa 36 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 37. sayfa 37 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 38. sayfa 38 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 39. sayfa 39 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 40. sayfa 40 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 41. sayfa 41 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 42. sayfa 42 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 43. sayfa 43 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 44. sayfa 44 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 45. sayfa 45 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 46. sayfa 46 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 47. sayfa 47 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 48. sayfa 48 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 49. sayfa 49 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 50. sayfa 50 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 51. sayfa 51 Actaris Doğalgaz Sayacı G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) 52. sayfa 52


Actaris G 25 SERİE 0 DÖNER PİSTONLU (ROTARY) Doğalgaz Sayacı

debits inverses eventuels.
4.1. 4 Emetteurs â moyenne & haute frequence (disponible en option)
Le compteur peut etre livre avec des emetteurs â moyenne ou haute frequence, de type inductif. Le 
branchement s'effectue sur un appareil possedant un circuit d"entree de type NAMUR.
4.1.5 Poids d'impulsions des emetteurs BF, MF et HF :voir l'annexe 1 
4.2 Filtre
Pour les compteurs equipes de brides, un joint filtre peut etre insere directement en amont du 
compteur â la place du joint d'etancheite standard. Ces filtres sont disponibles du DN 40 au DN150.
4.3 Cartouche silicagel externe 
Pour les conditions climatiques extremes, une cartouche silicagel externe peut etre installee sur les 
compteurs DN50 to DN150 lors de la fabrication.
   . 4 Brides
Des brides DN50 PN16 ou ANSI125 peuvent etre fournies pour adapter un compteur DN 40 
(connexions BSP) sur une conduite equipee de brides DN50. La distance entre brides est alors de 
171 mm.

5 M ise en service 
5.1 Generalites 
La procedure de mise en service depend toujours de la configuration de l'installation. Avant de 
mettre le compteur sous pression, le niveau de lubrifiant doit etre effectue. La pressurisation ou 
depressurisation doit etre effectuee graduellement : 0.3 bars / 5 P.S.I. par seconde au maximum. 
Apres mise en service, l'etancheite de l'installation doit etre verifiee.
La bonne installation et le bon fonctionnement du compteur peuvent etre verifies par un control 
visuel du totalisateur(pour verifier que le compteur tourne correctement) ainsi que par la mesure de 
la perte de charge du compteur en fonctionnement. L'utilisation de Pete's Plugs permet de realiser 
cette mesure alors que le compteur est sous pression (jusqu'â 20 bars).
5.2 Installation avec bi-pass :voir l'annexe 9
MISE EN SERVICE :
Proceder â la mise en service toutes vannes fermees.
-       Ouvrir lentement la vanne de bi-pass de façon â pressuriser la tuyauterie aval.
-       Lorsque la pression est equilibree en aval, ouvrir lentement le robinet V1. Les variations de
        pression ne doivent pas depasser 0.3 bars par seconde.
-       Lorsque la pression est equilibree dans le compteur, ouvrir lentement la vanne principale amont, puis
        fermer V1.
-       Ouvrir lentement la vanne aval et s'assurer que le compteur commence â enregistrer le debit.
-       Fermer progressivement la vanne de bi-pass. Verifier que le debit ne depasse pas la capacite du
        compteur.
MISE HORS SERVICE :
-       Ouvrir lentement la vanne de bi-pass puis fermer les vannes en amont et en aval du compteur.
-       Ouvrir legerement le robinet V2 et depressuriser le compteur. Les variations de pression ne
        doivent pas depasser 0.3 bars par seconde. S"assurer de la depressurisation complete du
        compteur.
File : DELTA_Instruction_manual_2008-01-21_T5E başvurusu i çin.doc                                                                                                                              5eite 11 von 52