Piller UB-R 625 KVA Kesintisiz Güç Kaynağı
KURULUM VE BAĞLANTILAR PILLER POWER SYSTEMS ÖNEMLİ Kablo sıcaklık üst limiti asgari 90° C olmalıdır. UPS-TİPİ Şebeke 140 Şebeke 2 / Çıkış Batarya L1-L3, N, PE L1-L3, N, PE + /- In In UB-S 150 280 A 217 A 330 A 1 x N2XCWY 4 x 95SM/50 1 x N2XCWY 4 x 70SM/3541 2* (1 x N2XY-0 1 x 95RM) 1 x N2XCWY 4 x 95SM/50 UB-S 220 410 A 318 A 483 A 1 x N2XCWY 4 x 150SM/70 2 x N2XCWY 4 x 70SM/35 2* (2 x N2XY-0 1 x 70RM) UB-S 330 606 A 476 A 713 A 2 x N2XCWY 4 x 120SM/70 2 x N2XCWY 4 x 95SM/50 2* (2 x N2XY-0 1 x 120RM) UB-S 420 771 A 606 A 908 A 3 x N2XCWY 4x95SM/50 2 x N2XCWY 4 x 120SM/7041 2* (2 x N2XY-0 1 x 150RM) 2 x N2XCWY 4 x 150SM/70 UB-S 500 918 A 722 A 1081 A 4 x N2XCWY 4x95SM/50 3 x N2XCWY 4 x 120SM/70 2* (3 x N2XY-0 1 x 120RM) UB-S 625 1148 A 902 A 1351 A 4 x N2XCWY 4x120SM/70 4 x N2XCWY 4 x 120SM/70 2* (4 x N2XY-0 1 x 120RM) UB-S 800 1458 A 1155 A 1711 A 5 x N2XCWY 4 x 150SM/70 4 x N2XCWY 4 x 150SM/7041 2* (5 x N2XY-0 1 x 120RM) 5 x N2XCWY 4 x 120SM/70 UB-S 1100 1998 A 1588 A 2353 A 7 x N2XCWY 4 x 150SM/70 5 x N2XCWY 4 x 150SM/7041 2* (6 x N2XY-0 1 x 150RM) 6 x N2XCWY 4 x 150SM/70 NOT Trip Akımı ≤ 1.45 x In In = Koruyucu cihazın anma akımı 40 Sadece kısa devre koruması gereklidir 41 Anma Akımları Bölüm 4’deki Giriş verileri tablosundaki gibi olan gL/gG tip L.V.H.R.C. sigortaları, VDE 0100 bölüm 430’e göre bu kablonun aşırı yük koruması için uygun değildirler. 91.9.045.0190 6.0 29.07.10 4-79