Piller UB-R 330 KVA Kesintisiz Güç Kaynağı
KURULUM VE BAĞLANTILAR PILLER POWER SYSTEMS 4.3.5.1 UB-R / UB-S, Şebeke 1 ve Şebeke 2 için ortak besleme ÖNEMLİ Kablo sıcaklık üst limiti asgari 70° C olmalıdır. UPS-TİPİ Şebeke 1 Çıkış Batarya L1-L3, N, PE L1-L3, N, PE + /- In In UB150 280 A 217 A 330 A 1 x NYCWY 4 x 120SM/70 1 x NYCWY 4 x 120SM/70 2* (1 x NYY-0 1 x 150RM) UB220 410 A 318 A 483 A 2 x NYCWY 4 x 95SM/50 2 x NYCWY 4 x 95SM/50 2* (2 x NYY-0 1 x 95RM) UB330 606 A 476 A 713 A 3 x NYCWY 4 x 95SM/5036 3 x NYCWY 4 x 95SM/5036 2* (3 x NYY-0 1 x 95RM) 3 x NYCWY 4 x 120SM/70 3 x NYCWY 4 x 120SM/70 UB420 771 A 606 A 908 A 3 x NYCWY 4x150SM/7036 3 x NYCWY 4 x 150SM/70362* (3 x NYY-0 1 x 150RM) 4 x NYCWY 4x120SM/70 4 x NYCWY 4 x 120SM/70 UB500 918 A 722 A 1081 A 4 x NYCWY 4x150SM/7036 4 x NYCWY 4 x 150SM/70362* (4 x NYY-0 1 x 120RM) 5 x NYCWY 4x120SM/70 5 x NYCWY 4 x 120SM/70 UB625 1148 A 902 A 1351 A 5 x NYCWY 4x150SM/7036 5 x NYCWY 4 x 150SM/70362* (5 x NYY-0 1 x 120RM) 6 x NYCWY 4x150SM/70 6 x NYCWY 4 x 150SM/70 UB800 1458 A 1155 A 1711 A 7 x NYCWY 4 x 150SM/70 7 x NYCWY 4 x 150SM/70 2* (6 x NYY-0 1 x 150RM) UB1100 1998 A 1588 A 2353 A 9 x NYCWY 4 x 150SM/70 9 x NYCWY 4 x 150SM/70 2* (7 x NYY-0 1 x 150RM) NOT Trip Akımı ≤ 1.45 x In In = Koruyucu cihazın anma akımı 36 Anma Akımları Bölüm 4’deki Giriş verileri tablosundaki gibi olan gL/gG tip L.V.H.R.C. sigortaları, VDE 0100 bölüm 430’e göre bu kablonun aşırı yük koruması için uygun değildirler. 91.9.045.0190 6.0 29.07.10 4-76