Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 1. sayfa 1 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 2. sayfa 2 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 3. sayfa 3 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 4. sayfa 4 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 5. sayfa 5 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 6. sayfa 6 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 7. sayfa 7 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 8. sayfa 8 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 9. sayfa 9 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 10. sayfa 10 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 11. sayfa 11 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 12. sayfa 12 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 13. sayfa 13 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 14. sayfa 14 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 15. sayfa 15 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 16. sayfa 16 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 17. sayfa 17 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 18. sayfa 18 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 19. sayfa 19 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 20. sayfa 20 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 21. sayfa 21 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 22. sayfa 22 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 23. sayfa 23 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 24. sayfa 24 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 25. sayfa 25 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 26. sayfa 26 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 27. sayfa 27 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 28. sayfa 28 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 29. sayfa 29 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 30. sayfa 30 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 31. sayfa 31 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 32. sayfa 32 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 33. sayfa 33 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 34. sayfa 34 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 35. sayfa 35 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 36. sayfa 36 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 37. sayfa 37 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 38. sayfa 38 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 39. sayfa 39 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 40. sayfa 40 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 41. sayfa 41 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 42. sayfa 42 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 43. sayfa 43 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 44. sayfa 44 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 45. sayfa 45 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 46. sayfa 46 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 47. sayfa 47 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 48. sayfa 48 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 49. sayfa 49 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 50. sayfa 50 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 51. sayfa 51 Actaris Doğalgaz Sayacı G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) 52. sayfa 52


Actaris G 400 S3-FLOW DÖNER PİSTONLU (ROTARY) Doğalgaz Sayacı

qui est equipe d'un raccordement interne. 
Avant l'installation: Les operations de remplissage et de vidange doivent etre effectuees lorsque le 
compteur est installe sur la conduite, sans pression. L'utilisation de Pete's Plugs permet de realiser 
les niveaux de lubrifiant alors que le compteur est sous pression (jusqu'â 20 bars). Voir l'annexe 7. 
Le niveau est correct lorsque le niveau de lubrifiant traverse le centre du voyant.
Pour le compteur DN 40, le niveau du lubrifiant â ajuster depend du sens du debit (horizontal ou 
vertical).
Pour les compteurs en acier, le bouchon de niveau est utilise comme trop plein.
Pour les compteurs equipes de l'option multi-positions, il faut s'assurer que les voyants avant et 
arriere se trouvent dans la position qui correspond â l'utilisation du compteur. Le cas echeant, il faut 
proceder â une inversion des voyants et du bouchon correspondant. Lorsqu'il est necessaire 
d'inverser un voyant et un bouchon, il est recommande de remplacer les joints d'etancheite 
correspondants. Dans le cas oû le voyant arriere n'est pas visible, il faut proceder de la façon 
suivante :
-  Depressuriser le compteur.
-  Vidanger le carter arriere.
-  A l'aide d'un recipient gradue, remplir le carter arriere en respectant le volume defini dans
   l'annexe 5.

4 Accessoires 
4.1 Accessoires electriques
Instructions pour l'utilisation en atmospheres potentiellement explosives (ATEX) :
-  Les emetteurs d'impulsions ne doivent etre raccordes qu'â des appareils homologues de securite
   intrinseque suivant l'EN 50020.
-  Nettoyer le totalisateur uniquement avec un chiffon humide.
-  La surface exterieure des pieces en aluminium situees dans les environs immediats du compteur
   doit etre protegee par un traitement adequat (par exemple peinture) si une pellicule oxydee peut 
   s'y deposer.
-  Le compteur doit etre relie electriquement â la terre.
-  Pour le montage, demontage ou reparation sur site du compteur, uniquement des outils
   autorises d'emploi en zone explosive peuvent etre utilises.
-  Le compteur ne doit pas etre expose aux flammes, radiations ionisantes, ultrasons ou â des
   champs electromagnetiques puissants.
4.1.1 Emetteur basse frequence (equipement standard)
Le compteur est livre avec un double emetteur d'impulsions â basse frequence. L"emetteur BF est 
constitue d"une ampoule Reed â contact sec normalement ouvert. Le schema de câblage est 
indique sur la plaque signaletique du compteur. Voir aussi l'annexe 8 pour de plus amples 
informations.
4.1.2 Surveillance de ligne
Les DN50 â DN150 sont livres en standard avec un contact de surveillance de ligne. Il s'agit d'une 
ampoule Reed â contact sec normalement ferme. Le schema de câblage est indique sur la plaque 
signaletique du compteur.
4.1.3 Capteur Cyble
Le capteur Cyble peut etre installe â n"importe quel moment sur le totalisateur, voir l"annexe 8. Le 
capteur Cyble est un emetteur d"impulsion sans rebond qui permet aussi de prendre en compte les
File : DELTA_Instruction_manual_2008-01-21_T5E başvurusu i çin.doc 5eite 10 von 52