Vaillant Kazan VKK 4706/3-E-HL 1. sayfa 1 Vaillant Kazan VKK 4706/3-E-HL 2. sayfa 2 Vaillant Kazan VKK 4706/3-E-HL 3. sayfa 3 Vaillant Kazan VKK 4706/3-E-HL 4. sayfa 4 Vaillant Kazan VKK 4706/3-E-HL 5. sayfa 5 Vaillant Kazan VKK 4706/3-E-HL 6. sayfa 6 Vaillant Kazan VKK 4706/3-E-HL 7. sayfa 7 Vaillant Kazan VKK 4706/3-E-HL 8. sayfa 8 Vaillant Kazan VKK 4706/3-E-HL 9. sayfa 9 Vaillant Kazan VKK 4706/3-E-HL 10. sayfa 10 Vaillant Kazan VKK 4706/3-E-HL 11. sayfa 11 Vaillant Kazan VKK 4706/3-E-HL 12. sayfa 12 Vaillant Kazan VKK 4706/3-E-HL 13. sayfa 13 Vaillant Kazan VKK 4706/3-E-HL 14. sayfa 14 Vaillant Kazan VKK 4706/3-E-HL 15. sayfa 15 Vaillant Kazan VKK 4706/3-E-HL 16. sayfa 16 Vaillant Kazan VKK 4706/3-E-HL 17. sayfa 17 Vaillant Kazan VKK 4706/3-E-HL 18. sayfa 18 Vaillant Kazan VKK 4706/3-E-HL 19. sayfa 19 Vaillant Kazan VKK 4706/3-E-HL 20. sayfa 20 Vaillant Kazan VKK 4706/3-E-HL 21. sayfa 21 Vaillant Kazan VKK 4706/3-E-HL 22. sayfa 22 Vaillant Kazan VKK 4706/3-E-HL 23. sayfa 23 Vaillant Kazan VKK 4706/3-E-HL 24. sayfa 24 Vaillant Kazan VKK 4706/3-E-HL 25. sayfa 25 Vaillant Kazan VKK 4706/3-E-HL 26. sayfa 26


Vaillant VKK 4706/3-E-HL Kazan

                                  Şartlar    Birim    3206/3-E-HL    3956/3-E-HL    4706/3-E-HL
 Isıl güç aralığı (kalorifer konumu)80/60      kW      63,0-315,2     77,8-389,1     92,6-463,0 
                                    60/40      kW      64,3-321,6     79,4-397,0     94,5-472,4 
                                    50/30      kW      65,9-329,6     81,4-406,9     96,8-484,1 
                                    40/30      kW      67,3-336,3     83,0-415,1     98,8-494,0
 Maks. Güç                           Hi        kW        320,0          395,0          470,0
 Min. Güç                            Hi        kW         64,0           79,0          94,0
 Katagori                                                      I2H
 Gaz giriş basıncı                  G20       Mbar                        20
 Atıkgaz sıcaklığı                  min        °C                       60-65
                                    Maks.      °C                       65-70
 CO2                                Qmin.    Vol %                       9,1
                                  Q maks.                                9,3
 Kazan karşı basıncı                           Pa          100,0          100,0        150,0

 NOx Sınıfı                                                               5
 NOx emisyon                      mg/kWh                                  60
 CO emisyon                       mg/kWh                                  20
 Nominal verimlilik                 80/60      %                         98,5 
                                    60/40      %                        100,5 
                                    50/30      %                        103,0 
                                    40/30      %                        105,1
 Maksimum kalorifer gidiş suyu                 °C                         85
 sıcaklığı
 Ayarlanabilir kalorifer gidiş suyu            °C                       35-85
 sıcaklığı
 Hazır bekleme kayıpları            70 °C      %                          0,4


 Elektrik bağlantıları
 Frekans                                      V/Hz                      230/50
 Maksimum güç                                  W            700           850          850
 Beklemede harcadığı güç                       W                          8
 Koruma sınıf                                                            IP20
 Sigorta                                                                 4AT




22                                                           Kullanım kılavuzu ecoCRAFT exclusiv 0020072951_00