Press ‘0’, ‘7’, ‘1’ keys in order and see ‘P-071’ on display. Pressing ‘Enter’ key,you will see the real time and date with the digit number belonging ten’s significant of day is blinking. 1 0 1 1 2 0 0 4 0 9 0 5 You can change the value of blinkink digit by pressing a numeric key or the same value to shift blinking one digit left and go on. Press ‘CLR’ to shift blinkink one position back,if you made a mistake when entering a digit. Pressing ‘Enter’ finishes clock setting with this setting.Control the setting by pressing ’5’ and see real time clock on the display. ENTERING CPU ADDRESS ON THE AUTOMATION (P-080) Communication between dispenser and site controller is half dublex type.This is a question- answer relationship between CPU and Site controller.(central computer) Site controller polls the necessary data from dispensers one by one by putting an address byte in the question messages.So,only addressed CPU answers this message. Thus,no data conflict occurs on communication line which is parallel connected to all dispensers’ CPU comm..ports. Addressing must be done carefully ,such that any two of Dispenser must not be at the same address. Procedure; Press ‘0’, ‘8’, ‘0’ keys in order and see ‘P-080’ on the display.Press ‘Enter’ and see display as shown below. Enter your password. P A S S When you are typing password, you will see ‘ o o o o o o’ instead of numbers. Press ‘Enter’ key. If your password is true,see the display form as shown below . A d d r E S S = X X The value in position ‘XX’ is current address value of this face of CPU changing between ‘00’ to ‘08’. Entering ‘00’ turns the CPU to manual mode and dispenser doesn’t answer messages sent by site controller. 48