W-2WAY ECO-i SYSTEM Unit Specifications
2. 4-Way Air Discharge Semi-concealed Type
Unit specifications (G)
MODEL No. Indoor Unit SPW-XDR364GXH56(A/B)
POWER SOURCE 220 - 230 - 240 V / single-phase / 50 Hz
PERFORMANCE Cooling Heating
Capacity kW 10.6 11.4
BTU / h 36,000 39,000
Air circulation (Hi / Me / Lo) m3 / h 1680 / 1380 / 1260
Moisture removal (High) Liters / h 3.9 –
ELECTRICAL RATINGS
Voltage rating V 220 230 240 220 230 240
Available voltage range V 198 - 264 198 - 264
Running amperes A 0.49 0.46 0.44 0.48 0.45 0.43
Power input W 70 69 69 62 60 60
Power factor % 65 65 65 59 58 58
Max. starting amperes A 1 1 1 1 1 1
FEATURES
Controls Microprocessor
Timer ON / OFF Timer (Max. 72 hr)
Fan speeds 3 and Automatic control
Air filter Washable, easy access, long life (2,500 hr)
Refrigerant control Electronic expansion valve
Operation sound (Hi / Me / Lo) dB-A 39 / 36 / 33
Refrigerant tubing connections Flare type
Refrigerant tube Liquid tube mm (in.) 9.52 (3 / 8)
diameter Gas tube mm (in.) 15.88 (5 / 8)
Drain connection 25 A, OD32 mm
Drain pump Max. head 64 cm above drain connection
Panel Optional (PNR-XD484GHA)
Remote controller Optional (RCS-SH80AG.WL)
Refrigerant tubing kit / Accessories Optional / –
Color (Approximate value) Munsell 2.5GY 9.0 / 0.5, RAL 9001-GL (resemblant color) 4
DIMENSIONS & WEIGHT Indoor unit (including panel) Body Package Panel
Height mm (in.) 354 (13-30 / 32) 346 (13-20 / 32) 104 (4-3 / 32)
Unit dimensions Width mm (in.) 950 (37-13 / 32) 892 (35-4 / 32) 1008 (39-22 / 32)
Depth mm (in.) 950 (37-13 / 32) 905 (35-20 / 32) 990 (38-31 / 32)
Net weight kg (lbs.) 30.5 (67) – –
Shipping weight kg (lbs.) – 30 (66) 7 (16)
Shipping volume m3(cu.ft) – 0.279 (9.9) 0.104 (3.8)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27°C DB / 19°C WB; Outdoor air temperature 35°C DB
Heating: Indoor air temperature 20°C DB; Outdoor air temperature 7°C DB / 6°C WB
4-33