Kullanım Kılavuzları
W-2WAY ECO-i SYSTEM Unit Specifications 6. Ceiling-Mounted Type Unit specifications (F) MODEL No. Indoor Unit SPW-TDR484GXH56(A/B) POWER SOURCE 220 - 230 - 240 V / single-phase / 50 Hz PERFORMANCE Cooling Heating Capacity kW 14 16.0 BTU / h 47,800 54,600 Air circulation (Hi / Me / Lo) m3 / h 1800 / 1560 / 1320 Moisture removal (High) Liters / h 5.6 – ELECTRICAL RATINGS Voltage rating V 220 230 240 220 230 240 Available voltage range V 198 - 264 198 - 264 Running amperes A 0.69 0.63 0.60 0.69 0.63 0.62 Power input W 85 86 88 84 85 86 Power factor % 56 59 61 55 59 58 Max. starting amperes A 3 3 3 3 3 3 FEATURES Controls Microprocessor Timer ON / OFF Timer (Max. 72 hr) Fan speeds 3 and Automatic control Air filter Washable, easy access, long life (2,500 hr) Refrigerant control Electronic expansion valve Operation sound (Hi / Me / Lo) dB-A 43 / 40 / 37 Refrigerant tubing connections Flare type Refrigerant tube Liquid tube mm (in.) 9.52 (3 / 8) diameter Gas tube mm (in.) 15.88 (5 / 8) Drain connection 20 A, OD26 mm Remote controller Optional (RCS-TRP80ANG.WL) Refrigerant tubing kit / Accessories Optional / – Color (Approximate value) Munsell 10Y 9.0 / 0.4, RAL 9010-GL DIMENSIONS & WEIGHT Unit dimensions Package dimensions 4 Height mm (in.) 210 (8-9 / 32) 280 (11-1 / 32) Unit dimensions Width mm (in.) 1595 (62-25 / 32) 1670 (65-24 / 32) Depth mm (in.) 680 (26-25 / 32) 780 (30-23 / 32) Net weight kg (lbs.) 33 (73) Shipping weight kg (lbs.) 37 (82) Shipping volume m3(cu.ft) 0.365 (12.9) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Rated conditions Cooling: Indoor air temperature 27°C DB / 19°C WB; Outdoor air temperature 35°C DB Heating: Indoor air temperature 20°C DB; Outdoor air temperature 7°C DB / 6°C WB 4-94