W-2WAY ECO-i SYSTEM Unit Specifications
6. Ceiling-Mounted Type
Unit specifications (D)
MODEL No. Indoor Unit SPW-TDR254GXH56(A/B)
POWER SOURCE 220 - 230 - 240 V / single-phase / 50 Hz
PERFORMANCE Cooling Heating
Capacity kW 7.3 8.0
BTU / h 25,000 27,000
Air circulation (Hi / Me / Lo) m3 / h 1110 / 900 / 840
Moisture removal (High) Liters / h 3.0 –
ELECTRICAL RATINGS
Voltage rating V 220 230 240 220 230 240
Available voltage range V 198 - 264 198 - 264
Running amperes A 0.38 0.35 0.33 0.38 0.35 0.34
Power input W 43 43 44 42 42 43
Power factor % 51 53 56 50 52 53
Max. starting amperes A 2 2 2 2 2 2
FEATURES
Controls Microprocessor
Timer ON / OFF Timer (Max. 72 hr)
Fan speeds 3 and Automatic control
Air filter Washable, easy access, long life (2,500 hr)
Refrigerant control Electronic expansion valve
Operation sound (Hi / Me / Lo) dB-A 38 / 36 / 33
Refrigerant tubing connections Flare type
Refrigerant tube Liquid tube mm (in.) 9.52 (3 / 8)
diameter Gas tube mm (in.) 15.88 (5 / 8)
Drain connection 20 A, OD26 mm
Remote controller Optional (RCS-TRP80ANG.WL)
Refrigerant tubing kit / Accessories Optional / –
Color (Approximate value) Munsell 10Y 9.0 / 0.4, RAL 9010-GL
DIMENSIONS & WEIGHT Unit dimensions Package dimensions
4 Height mm (in.) 210 (8-9 / 32) 280 (11-1 / 32)
Unit dimensions Width mm (in.) 1180 (46-15 / 32) 1255 (49-13 / 32)
Depth mm (in.) 680 (26-25 / 32) 780 (30-23 / 32)
Net weight kg (lbs.) 25 (55)
Shipping weight kg (lbs.) 28 (62)
Shipping volume m3(cu.ft) 0.274 (9.7)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27°C DB / 19°C WB; Outdoor air temperature 35°C DB
Heating: Indoor air temperature 20°C DB; Outdoor air temperature 7°C DB / 6°C WB
4-92