W-2WAY ECO-i SYSTEM Unit Specifications
3. 2-Way Air Discharge Semi-concealed Type
Unit specifications (B)
MODEL No. Indoor Unit SPW-SR94GXH56(A/B)
POWER SOURCE 220 - 230 - 240 V / single-phase / 50 Hz
PERFORMANCE Cooling Heating
Capacity kW 2.8 3.2
BTU / h 9,600 11,000
Air circulation (Hi / Me / Lo) m3 / h 540 / 480 / 420
Moisture removal (High) Liters / h 1.0 –
ELECTRICAL RATINGS
Voltage rating V 220 230 240 220 230 240
Available voltage range V 198 - 264 198 - 264
Running amperes A 0.44 0.45 0.45 0.28 0.29 0.30
Power input W 86 92 97 55 60 64
Power factor % 89 89 90 89 90 89
Max. starting amperes A 1 1 1 1 1 1
FEATURES
Controls Microprocessor
Timer ON / OFF Timer (Max. 72 hr)
Fan speeds 3 and Automatic control
Airflow direction Automatic (Remote control)
Air filter Washable, easy access, long life (2,500 hr)
Refrigerant control Electronic expansion valve
Operation sound (Hi / Me / Lo) dB-A 33 / 29 / 26
Refrigerant tubing connections Flare type
Refrigerant tube Liquid tube mm (in.) 6.35 (1 / 4)
diameter Gas tube mm (in.) 12.7 (1 / 2)
Drain connection 25 A, OD32 mm
Drain pump Max. head 50 cm above drain connection
Panel Optional (PNR-S183GHAN)
Remote controller Optional (RCS-TH80AG.WL)
4 Refrigerant tubing kit / Accessories Optional / –
Color (Approximate value) Munsell 10Y 9.3 / 0.4, RAL 9010-GL
Package
DIMENSIONS & WEIGHT Indoor unit (including panel) Body Panel
Height mm (in.) 358 (14-3 / 32) 310 (12-7 / 32) 165 (6-16 / 32)
Unit dimensions Width mm (in.) 1060 (41-23 / 32) 1082 (42-19 / 32) 1147 (45-5 / 32)
Depth mm (in.) 680 (26-25 / 32) 658 (25-29 / 32) 789 (31-20 / 32)
Net weight kg (lbs.) 30 (66) – –
Shipping weight kg (lbs.) – 26 (57) 11 (24)
Shipping volume m3(cu.ft) – 0.221 (7.8) 0.149 (5.3)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27°C DB / 19°C WB; Outdoor air temperature 35°C DB
Heating: Indoor air temperature 20°C DB; Outdoor air temperature 7°C DB / 6°C WB
4-50