KURULUM VE BAĞLANTILAR PILLER POWER SYSTEMS
4.3.5.1 UB-R / UB-S, Şebeke 1 ve Şebeke 2 için ortak besleme
ÖNEMLİ Kablo sıcaklık üst limiti asgari 70° C olmalıdır.
UPS-TİPİ Şebeke 1 Çıkış Batarya
L1-L3, N, PE L1-L3, N, PE + /-
In In
UB150 280 A 217 A 330 A
1 x NYCWY 4 x 120SM/70 1 x NYCWY 4 x 120SM/70 2* (1 x NYY-0 1 x 150RM)
UB220 410 A 318 A 483 A
2 x NYCWY 4 x 95SM/50 2 x NYCWY 4 x 95SM/50 2* (2 x NYY-0 1 x 95RM)
UB330 606 A 476 A 713 A
3 x NYCWY 4 x 95SM/5036 3 x NYCWY 4 x 95SM/5036 2* (3 x NYY-0 1 x 95RM)
3 x NYCWY 4 x 120SM/70 3 x NYCWY 4 x 120SM/70
UB420 771 A 606 A 908 A
3 x NYCWY 4x150SM/7036 3 x NYCWY 4 x 150SM/70362* (3 x NYY-0 1 x 150RM)
4 x NYCWY 4x120SM/70 4 x NYCWY 4 x 120SM/70
UB500 918 A 722 A 1081 A
4 x NYCWY 4x150SM/7036 4 x NYCWY 4 x 150SM/70362* (4 x NYY-0 1 x 120RM)
5 x NYCWY 4x120SM/70 5 x NYCWY 4 x 120SM/70
UB625 1148 A 902 A 1351 A
5 x NYCWY 4x150SM/7036 5 x NYCWY 4 x 150SM/70362* (5 x NYY-0 1 x 120RM)
6 x NYCWY 4x150SM/70 6 x NYCWY 4 x 150SM/70
UB800 1458 A 1155 A 1711 A
7 x NYCWY 4 x 150SM/70 7 x NYCWY 4 x 150SM/70 2* (6 x NYY-0 1 x 150RM)
UB1100 1998 A 1588 A 2353 A
9 x NYCWY 4 x 150SM/70 9 x NYCWY 4 x 150SM/70 2* (7 x NYY-0 1 x 150RM)
NOT Trip Akımı ≤ 1.45 x In
In = Koruyucu cihazın anma akımı
36 Anma Akımları Bölüm 4’deki Giriş verileri tablosundaki gibi olan gL/gG tip L.V.H.R.C. sigortaları, VDE 0100 bölüm 430’e göre bu
kablonun aşırı yük koruması için uygun değildirler.
91.9.045.0190 6.0 29.07.10
4-76